SPCC secondary containment calculation for drums and IBCs

How the EPA’s SPCC rule sizes containment for drums and IBCs, how it differs from the RCRA and fire code figures, and the calculator set up for each.

Under the EPA’s SPCC rule, secondary containment must hold the entire capacity of the largest single container, plus enough freeboard for rain. It applies at facilities storing more than 1,320 US gallons of oil above ground, counting only containers of 55 gallons or more. Four 55-gallon drums on one pallet need 55 gallons plus freeboard, not 110 per cent of the total.

Open the calculator for the US Hazardous waste Flammable liquids

Secondary containment for common stores

Oil under SPCC, and hazardous waste under RCRA, for 55-gallon drums and 275- and 330-gallon IBCs. Outdoors, add freeboard for rain to the SPCC figure.

StoreStoredSPCC, oilRCRA, hazardous wasteCalculator
One 55-gallon drum55 gal55 gal (208 L) + rain55 galOpen
Four 55-gallon drums220 gal55 gal (208 L) + rain55 galOpen
One 275-gallon IBC275 gal275 gal (1,041 L) + rain275 galOpen
Two 275-gallon IBCs550 gal275 gal (1,041 L) + rain275 galOpen
One 330-gallon IBC330 gal330 gal (1,249 L) + rain330 galOpen
Four drums and one 330-gallon IBC550 gal330 gal (1,249 L) + rain330 gal–

US gallons. 55 gallons is 208 litres. The calculator works in litres and converts.

Does SPCC apply, and what it asks forFour checks: oil stored above ground over 1,320 US gallons, counting only containers of 55 gallons or more, a facility that could discharge to navigable waters, then containment for the largest container plus rain. Over 1,320 gal
Oil stored above ground at the facility
55 gal and up
Only these containers count
Could reach water
Navigable waters or shorelines
Size it
Largest container plus rain
Smaller containers stay outside the count, which is why a store of 20-litre cans rarely brings a facility into the rule.

Three federal and model rules, three figures

SPCC (40 CFR 112) sizes on the largest container plus freeboard, for oil. RCRA sizes permitted hazardous waste storage on 10 per cent of the total or the largest container, whichever is greater. The International Fire Code, which states and cities adopt, asks for containment above set quantities of flammable and hazardous liquids and adds 20 minutes of sprinkler water indoors, or the 24-hour rainfall from a 25-year storm outdoors. Outdoors, it accepts an approved containment pallet with a sump of at least 66 gallons, kept out of the rain.

The calculator applies all three: pick the United States, then the liquid.

Working it out by hand

  1. Check the facility total: more than 1,320 gallons above ground, in containers of 55 gallons or more.
  2. Find the largest container in each containment area.
  3. Size the containment to hold all of it.
  4. Outdoors, add freeboard for the rain your plan uses, often a 25-year, 24-hour storm.
  5. Keep the calculation on file for an inspector. The rule does not require it in the plan.

Sizing a dike around tanks: EPA’s worked example

A dike around several tanks loses room to every tank inside it except the largest, whose spill it must hold. EPA’s sample worksheet for three horizontal tanks in a rectangular dike shows the method in cubic feet. Its dike measures 20 by 15 feet with 3-foot walls; tanks A and B hold 2,500 gallons each and tank C holds 500.

StepWorkingResult
Dike volume20 × 15 ft × 3 ft900 ft³
Largest tank2,500 gal × 0.1337 ft³ a gallon334 ft³
Tank B below the wall24 in of its 78 in diameter: 26.3% of 334 ft³88 ft³
Tank C below the wall24 in of its 48 in diameter: 50% of 67 ft³34 ft³
Net capacity900 less 88 less 34778 ft³
Rain7 in from a 24-hour, 25-year storm, 0.6 ft over 300 ft²180 ft³
NeededLargest tank plus rain, 334 + 180514 ft³

The share of a horizontal tank below the wall comes from its height-to-diameter ratio, read from a table in the worksheet; a tank half below the wall takes half its volume. EPA’s worksheets assume a flat floor, walls of one height and square corners, and leave out tank supports and foundations, so a Professional Engineer certifying a plan adjusts them to the site.

EPA’s three-tank dike, worked From EPA’s sample SPCC worksheet: a 20 by 15 foot dike with 3 foot walls around three horizontal tanks, its net capacity after the smaller tanks’ displacement, and what the largest tank plus a 7 inch storm need. EPA’S THREE-TANK DIKE, WORKED Dike volume 900 ft³ Taken by tanks B and C 122 ft³ Net capacity 778 ft³ Largest tank 334 ft³ Rain from the storm 180 ft³ Needed 514 ft³
The net capacity clears the need by 264 cubic feet, so the dike passes with the storm included.

A spill pallet skips the displacement step. The drums stand on a grate above the sump, so the whole sump counts, and a pallet kept out of the rain needs no freeboard: EPA asks for rain capacity only where rain can collect. Who needs a plan at all, and how the 1,320-gallon count works, is in our guide to the SPCC rule.

Common questions

How do you calculate SPCC secondary containment?

Take the capacity of the largest single container in the containment area and add enough freeboard to hold rain. Four 55-gallon drums on one pallet need 55 gallons plus freeboard. The rule sets no freeboard figure; EPA guidance points to the rainfall from a 25-year, 24-hour storm for outdoor containment.

Is SPCC secondary containment 110 per cent?

No. The rule asks for the entire capacity of the largest container plus sufficient freeboard for precipitation. 110 per cent is a common rule of thumb for that freeboard, and some state rules and permits write it in, but the federal rule does not.

Does SPCC apply to my facility?

It applies where a facility stores more than 1,320 US gallons of oil above ground and could reasonably be expected to discharge oil to navigable waters or shorelines. Only containers of 55 gallons or more count towards the 1,320.

What about hazardous waste in drums?

Permitted hazardous waste storage under RCRA needs containment of 10 per cent of the total or 100 per cent of the largest container, whichever is greater. A generator storing under 40 CFR 262.17 has no federal capacity figure, so check your state.

How do you allow for other tanks inside a dike?

Subtract the volume each one takes up below the top of the dike wall, leaving out the largest tank, whose spill the dike must hold. For a horizontal tank, EPA’s worksheet divides its height below the wall by its diameter and reads the share of its volume from a table: a tank half below the wall takes half its volume.

What rain event should SPCC containment hold?

The rule names none and leaves the figure to the owner or operator. EPA’s worksheets note that industry often uses 110 per cent of the tank as a rule of thumb. They add that this may fall short of a typical storm in a wet area, and that a 24-hour, 25-year storm gives a conservative figure. NOAA, airports and water authorities publish rainfall data.

Must the containment calculation go in the SPCC plan?

No. EPA notes that the rule does not require the calculation in the plan, but advises keeping it on file to show an inspector that the containment complies. A Professional Engineer certifying the plan may adapt EPA’s sample worksheets to the site.

References

The standards and regulations this page relies on, at their issuing body. Where a market rule is named here, check the current revision before you specify against it.

Figures worked out by our spill pallet calculator, applying each rule as read from the official text on 3 October 2026.